Field Setting from Outdoor Unit
SiUS341802EC
187
Part 5 Field Settings and Test Operation
When operation parameters return to normal range, the capacity priority is switched OFF, enable to
reduce airflow rate depending on night-time low noise operation is still required (end time for
night-time low noise operation is not reached or external input night-time low noise operation is still
closed).
[2-29]:
Capacity priority
When the night-time low noise operation is in use, performance of system might
drop because airflow rate of outdoor unit is reduced.
Default value: 0. Capacity priority cannot be used.
Field setting 1: Capacity priority can temporary cancel the night-time low noise
operation. Capacity priority can be initiated when certain operation parameters
approach the safety setting:
Raise in high pressure during cooling.
Drop in low pressure during heating.
Raise of discharge pipe temperature.
Raise of inverter current.
Raise of fin temperature inverter PCB.
Operation
sound
Rated
Level 1
Level 2
Level 3
Time set with "Night-time low
noise operation start setting"
Low noise mode
instructing
Operation sound set with
"External low noise setting"
10:00 PM
8:00 PM
12:00 AM
6:00 AM 7:00 AM 8:00 AM
Set with "Night-time low noise operation start
setting". (Factory setting is "10:00 PM".)
Set with "Night-time low noise operation end
setting". (Factory setting is "8:00 AM".)
*
Low noise
mode instructing
*
Operation sound set with
"External low noise setting"
*
Night-time
If capacity priority is set in
"Capacity priority setting", the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
Time set with "Night-time low
noise operation end setting"
*
Operation sound mode
set with "Night-time low
noise operation setting"
[2-30]:
Power consumption limitation level (step 1) via the external control adaptor
(DTA104A61/62)
If the system needs to run under power consumption limitation conditions when an
external signal is sent to the unit, this setting defines the level power consumption
limitation that will be applied for step 1. The level is according to the table.
Default value: 3
Change [2-30]: 1, 2, 3, 4, 5, 6, 7, or 8 in function of required limitation
Value
[2-30]
Power consumption limitation (approximately)
1
60%
2
65%
3 (default)
70%
4
75%
5
80%
6
85%
7
90%
8
95%
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...