Check
SiUS341802EC
377
Part 6 Service Diagnosis
4.5 Refrigerant Overcharge Check
CHECK 6
In case of
VRV
Systems, the only way to judge as the overcharge of refrigerant is with operating
conditions due to the relationship to pressure control and electronic expansion valve control.
As information for making a judgment, refer to the information below.
Diagnosis of refrigerant overcharge
1. High pressure rises. Consequently, overload control is conducted to cause insufficient cooling
capacity.
2. The superheating degree of suction gas lowers (or wet operation is performed).
Consequently, the compressor becomes lower in discharge pipe temperature despite of
pressure loads.
3. The subcooling degree of condensate rises. Consequently, in heating, the temperature of
discharge air through the subcooled section becomes lower.
Cooling
High pressure
Lo
w
pressure
Frequency
High pressure
gradually rises
w
ith
increase in
frequency.
Subcooling degree
becomes higher.
(Liquid connection
pipe temperature
lo
w
ers.)
Lo
w
pressure rises due
to decreased
compressor output.
High pressure
Lo
w
pressure
Frequency
Heating
The outdoor unit electronic expansion valve
is closed due to the overload control.
Frequency comes to
the minimum level.
(
High pressure
is maintained
at a constant level.)
Lo
w
pressure
rises
due to
decreased
frequency.
To maintain
high pressure
,
frequency
decreases
under the
capacity control.
High pressure
drops or rises
immediately after the overload
control is complete.
Lo
w
pressure
drops due to
closed outdoor unit
electronic expansion valve.
Hot gas bypass is activated
for
lo
w
pressure
protection,
i.e., hunting at
lo
w
pressure
.
Higher degree of overcharge
(Degree of overcharge)
Proper amount
To maintain lo
w
pressure, frequency
increases under the capacity
control.
Frequency comes to
the minimum level.
High pressure
dropping control
(Lo
w
pressure is
maintained at a
constant level.)
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...