Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
190
Automatic lockout
When this setting is made, the auto-backup function will automatically be activated. This will allow
the auxiliary or secondary heat source to be automatically energized in the event of a system failure
related to outdoor units.
Error codes capable of auto-backup are listed in the table below. Please be aware that the error
codes that are not listed do not auto-backup in order to protect the unit.
Error code
(Auto backup
possible)
Error contents
A3
Drain level control system abnormality
E3
Actuation of high pressure switch
E4
Actuation of low pressure sensor
E5
Compressor motor lock
E6
Compressor damage alarm
E7
Outdoor fan motor abnormality
E9
Electronic expansion valve coil abnormality
F3
Discharge pipe temperature abnormality
F4
Wet alarm
H3
Harness abnormality (between outdoor unit main PCB and inverter PCB)
H7
Outdoor fan PCB abnormality
H9
Outdoor air thermistor (R1T) abnormality
J3
Discharge pipe thermistor (R21T) abnormality
Compressor body thermistor (R14T) abnormality
J5
Compressor suction thermistor (R12T) abnormality
Suction pipe thermistor (R10T) abnormality
J6
Heat exchanger deicer thermistor (R11T) abnormality
Heat exchanger gas pipe thermistor (R8T, R9T) abnormality
J7
Receiver inlet thermistor (R3T) abnormality
Subcooling heat exchanger liquid pipe thermistor (R7T) abnormality
Subcooling injection thermistor (R16T) abnormality
J8
Heat exchanger liquid pipe thermistor (R4T, R5T) abnormality
Leak detection thermistor (R15T) abnormality
J9
Subcooling heat exchanger gas pipe thermistor (R6T) abnormality
Receiver gas purge thermistor (R13T) abnormality
JA
High pressure sensor abnormality
JC
Low pressure sensor abnormality
L1
Inverter PCB abnormality
L2
Momentary power failure during test operation
L3
Reactor temperature rise abnormality
L4
Inverter radiation fin temperature rise abnormality
L5
Compressor instantaneous overcurrent
L8
Compressor overcurrent
L9
Compressor startup abnormality
LC
Transmission error between inverter PCB and outdoor unit main PCB
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...