Si21-205
FFQ25/35/50/60BV1B
Removal Procedure
251
2. Installing the PC board
and re-wiring inside the
switch box
1
Engage the PC board
with two claws shown in
the right figure, push up
the board until a click
sound is generated,
then connect the lead
wires shown right.
2
Next connect the lead
wires in the route shown
below and fix them with
tie wrap in the following
order.
Connect the fan
motor lead wire to the
connector X20A.
Connect the lead wire
of capacitor for fan
motor to the
capacitor.
Insert the lead wire of
drain pump to the
connector X25A.
Connect the lead wire
of float switch to
X15A through the
specified path and
wire clamp
.
Insert two thermistors
to the connector
matching the color
with X17A and X18A
through the wire
clamp
(e.g.
connect the wire with
yellow tape to the
yellow connector).
Connect the lead wire of
float switch and two
pieces of wire of
thermistor to the switch
box by using tie wrap
.
(Use tie wrap properly to
prevent the wire from
contact with hot part of
the PC board.)
Insert the rubber bushing
of air temperature
thermistor
into the slit
of switch box.
Then, check that it is
connected to the
connector X19A.
Step
Procedure
Points
P1 P2F1 F2
X10A
X36A
X5A
X11A
X27A
Hooking claws for mounting PC board (Three locations)
Fixing claws for the PC board with pushing force upward
(Two locations)
(S2689)
Lead wire of swing motor
:X36A
High roltage cable of transformer :X11A
Low roltage cable of transformer
:X10A
Outdoor unit connection wire
:X27A
Wire of remote controller
:X5A
(S2690)
∗
Be careful that the lead wire does not lay off the groove.
To drain pump
To
float switch
S
Drain pump connector
V
Tie wrap
U
Heat exchanger
thermistor connectors
X17A, X18A
R
Lead wire of
capacitor for
fan motor
W
Rubber bushing for
air temp. thermistor
T
Connector X15A
for float switch
X
Tie wrap for low-tension
cable of transformer
Q
Fan motor lead wire X20A
To heat
exchanger
thermistor
Wire clamp
���
Slack wire here
if the wire is
excessively long.
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...