Outdoor Unit (25/35 class)
Si21-205
94
Function and Control
2.9
Fan Control
Outline
Fan control is carried out according to the following priority.
1. Fan ON control for electric component cooling fan
2. Fan control when defrosting
3. Fan OFF delay when stopped
4. ON/OFF control when cooling operation
5. Tap control when drooping function is working
6. Fan control when forced operation
7. Fan control during heating operation
8. Fan control for pressure difference upkeep
Detail
Fan OFF Control when Stopped
Fan OFF delay for 60 seconds must be made when the compressor is stopped.
2.10 Moisture Protection Function 1 (Securing of Differential
Pressure and Blown Air Temperature)
Outline
To secure the reliability of the compressor (for dryness of suction refrigerant and differential
pressure) which is the primary purpose of the compressor, the lower limit of the output
frequency is limited to two stages under the condition of outside air temperature. This time, in
addition to this purpose, this function is adopted also for prevention of cold draught by securing
the blown air temperature at the time of heating operation by low-temperature out side air.
Processing
1. At the first step
During operation of compressors.
Outdoor temperature
≤
DOA1CG
If
and
are under the simultaneous condition with AND, the lower limit of frequency in
this function is set at FCG7.
Compressors stop.
Outdoor temperature
≥
DOA2CG
If
and
are under the simultaneous condition with OR, the lower limit of frequency at the
first step control is cancelled.
2. At the second step
During operation of compressors
Outdoor temperature
≤
DOA3CG
If
and
are under the simultaneous condition with AND, the lower limit of frequency in
this function is set at FCG8.
Compressors stop.
Outdoor temperature
≥
DOA4CG
If
and
are under the coordinate condition with OR, the lower limit of frequency at the
second step control is cancelled.
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...