Outdoor Unit (25/35 class)
Si21-205
100
Function and Control
2.14 Malfunctions
2.14.1 Sensor Malfunction Detection
Sensor malfunction may occur either in the thermistor or current transformer (CT) system.
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Fin thermistor
4. Outdoor air thermistor
Relating to CT Malfunction
When the output frequency is more than 62 Hz and the input current is less than 0.5A, carry out
abnormal adjustment.
2.14.2 Detection of Overload and Over Current
Outline
In order to protect the inverter, detect an excessive output current, and for protecting
compressor, monitor the OL operation.
Detail
If the OL (compressor head) temperature exceeds 120~130˚C (depending on the
model), the compressor gets interrupted.
If the inverter current exceeds 22 A, the compressor gets interrupted too.
2.14.3 Insufficient Gas Control
Outline
If a power consumption is below the specified value in which the frequency is higher than the
specified frequency, it must be regarded as gas insufficient.
In addition to such conventional function, if the discharge temperature is higher than the target
discharge pipe temperature, and the electronic expansion valve is fully open (55 pulses) more
than the specified time, it is considered as an insufficient gas.
With the conventional function, a power consumption is weak comparing with that in the normal
operation when gas is insufficient, and gas insufficiency is detected by checking a power
consumption.
When operating with insufficient gas, although the rise of discharge pipe temperature is great
and the electronic expansion valve is open, it is presumed as an insufficient gas if the discharge
pipe temperature is higher than the target discharge pipe temperature.
Detail
Judgment by Input Current
When an output frequency is exceeds 65 Hz and the input current is less than specified value,
the adjustment is made for insufficient gas.
Judgment by Discharge Pipe Temperature
When discharge pipe temperature is 30˚C higher than target value and the electronic expansion
value opening is 55 plus (max.), the adjustment is made for insufficient gas.
Frequency
Power consumption
Insufficient gas zone
55 Hz
(R2834)
Gas insufficient
zone
(R1391)
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...