Troubleshooting for Outdoor Unit (50/60 class)
Si21-205
218
Troubleshooting
Troubleshooting
Check No.4
Refer to P.220
Check No.6
Refer to P.222
Check No.7
Refer to P.223
Check No.9
Refer to P.224
(R2855)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace the fan motor.
Repair the connector or fan
motor lead wires.
Replace the heat exchanger
thermistor.
Replace PCB.
Replace the electronic
expansion valve or coil.
Replace the PCB.
Change the air outlet grille
position.
Change the installation
location.
Clean the heat exchanger.
Check the installation space.
Check No.9
Outdoor fan check
Judgment
Check No.6
Heat exchanger thermistor check
Judgment
Check No.7
Installation condition
check
Check No.4
Electronic expansion valve check
Abnormal
Normal
Normal
Normal
Normal
Abnormal
Abnormal
Abnormal
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...