Error Codes and LED Indication
Si21-205
140
Troubleshooting
Indoor Unit
Indoor
Unit
LED
Display
Remote
Controller
Display
Location of Malfunction
Contents of Malfunction
Details of
Malfunction
(Reference
Page)
H1P
Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Controller
5
—
—
—
—
Normal
→
to outdoor unit
—
5
A1
—
—
—
Failure of indoor unit PC
board (For self-diagnosis by
LED, refer to p.138.)
142
4
3
5
A3
—
—
—
Malfunction of drain water
level system
143
5
AF
—
—
—
Float switch operation
during compressor stop
145
5
A6
(FHQ only)
—
—
Indoor unit fan motor
overload / overcurrent / lock
146,147
5
A7
—
—
Swing flap motor
Malfunction / Lock
149
5
AJ
—
—
Failure of capacity setting
151
5
C4
—
—
Malfunction of heat
exchanger temperature
sensor system (R2T)
152
5
C5
—
—
Malfunction of heat
exchanger temperature
sensor system (R3T)
153
5
C9
—
—
Malfunction of suction air
temperature sensor system
154
5
CJ
—
—
—
Malfunction of remote
control air temperature
sensor system
155
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...