Si21-205
Outdoor Unit (25/35 class)
Function and Control
91
2.4
Controls at Mode Changing / Start-up
2.4.1 Preheating Operation
Outline
Operate the inverter in the open phase operation with the conditions including the preheating
command (only for heat pump model) from the indoor, the outdoor air temperature and
discharge pipe temperature.
Detail
Preheating ON Condition
When outdoor air temperature is below 10.5ºC and discharge pipe temperature is below
10.5ºC, inverter in open phase operation starts.
OFF Condition
When outdoor air temperature is higher than 12ºC or discharge pipe temperature is higher
than 12ºC, inverter in open phase operation stops.
2.4.2 Four Way Valve Switching
Outline of
Heating
Operation
Heat Pump Only
During the heating operation current must not be conducted and during cooling and defrosting
current must be conducted. In order to eliminate the switching sound (as the four way valve coil
switches from ON to OFF) when the cooling is stopped, the delay switch of the four way valve
must be carried out after the operation stopped.
Detail
The OFF delay of four way valve
Energize the coil for 150 sec after unit operation is stopped.
2.4.3 Four Way Valve Operation Compensation
Outline
Heat Pump Only
At the beginning of the operation as the four way valve is switched, acquire the differential
pressure required for activating the four way valve by having output the operating frequency,
which is more than a certain fixed frequency, for a certain fixed time.
Detail
Staring Conditions
1. When starting compressor for cooling.
2. When the operating mode changes from the previous time.
3. When starting compressor for rushing defrosting or resetting.
4. When starting compressor for the first time after the reset with the power is ON.
Set the lower limit frequency to 66 (model by model) Hz for 45 seconds with the OR
conditions with 1 through 4 above.
2.4.4 3 Minutes Stand-by
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(Except when defrosting. (Only for Heat Pump Model).)
2.4.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting (only for heat pump model).)
FCG 3
FCG 2
FCG 1
TCG 1
TCG 2
TCG 3
94
96
50
240
240
120
Frequency
TCG1sec
Time
TCG2sec
TCG3sec
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...