Si21-205
Troubleshooting for Outdoor Unit (25/35 class)
Troubleshooting
183
6.13 Over-voltage Detection
Remote
Controller
Display
U2
Method of
Malfunction
Detection
An abnormal voltage rise is detected by checking the specified over-voltage detection circuit.
Malfunction
Decision
Conditions
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer
(The voltage is over 400V).
The system will be shut down if the error occurs 5 times.
Clearing condition: Continuous run for about 60 minutes (normal)
Supposed
Causes
Supply voltage not as specified
Over-voltage detection circuit defective
PAM control part(s) defective
Troubleshooting
Note:
If the model doesn’t have SPM, replace the outdoor unit PCB.
Check the supply voltage.
Correct the power supply.
Check for such factors for a
long term.
Replace the SPM.
(Replace the outdoor unit
PCB.)
(R2957)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Supply voltage as
specified?
NO
YES
Turn on the
power again.
Error displayed again?
YES
Repeat a
couple of times.
NO
Disturbance factors
∗
Noise
∗
Power supply distortion
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...