Method of Field Set (Reset after Maintenance Inspection/Repair)
Si21-205
58
Field Setting
1.4
Local Setting Mode No.
Example
To set the filter sign time to “filter contamination - heavy” for all units in a group:
Set mode No. to “10,” setting switch No. to “0,” and setting position No. to “02.”
Table (FHQ & FFQ)
Mode
No.
Note 1
Setting
Switch
No.
Setting Description
Setting Position No. *Note 2
01
02
03
10
(20)
0
Filter contamination - heavy /
light (Setting of operating
hours for filter sign indication)
(Change setting when
reducing filter sign indication
time to half due to quick soiling
of filter)
Long-Life
Type
Light
Approx.
2,500
hours
Heavy
Approx.
1,250
hours
—
1
Long-life filter type (Setting of filter sign
indication time)
(Change setting when Ultra-long-life filter is
installed)
Long-Life Filter
—
—
2
Remote control thermostat
(Set when remote control thermostat sensor
is used.)
Use
Not use
3
Estimation of filter operating hour
(Change setting when filter sign indication is
not used)
ON
OFF
—
11
(21)
2
Indoor unit fan OFF when thermostat OFF
in cooling/heating
—
Fan OFF
—
12
(22)
5
Automatic restart after power failure reset
*Note 4
OFF
ON
—
13
(23)
0
High
Ceiling
Ceiling-suspended type(FHQ
only)
2.7 m or Lower
2.7~3.5 m
—
1
Air flow direction selection (Change setting
when blocking kit is installed) *Note 3
F
T
W
4
Setting of air flow direction adjustment
range
Upward
Standard
Downward
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...