Si21-205
Outdoor Unit (50/60 class)
Function and Control
103
3.1.2 Cooling Only Model
A Outdoor Heat
Exchanger
Thermistor (DCB)
1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature.
Set a target discharge temperature depending on the outdoor and indoor heat exchanger
temperature.
Control the electronic expansion valve opening so that the target discharge temperature can
be obtained.
2. When cooling: an outdoor heat exchanger thermistor is used for detecting the discharge
thermistor disconnected.
When the temperature of the discharge piping is lower than the temperature of outdoor heat
exchanger, a disconnected discharge thermistor can be detected.
3. The outdoor heat exchanger thermistor is used for high pressure protection during cooling
operation.
B Discharge
Pipe Thermistor
(DOT)
1. The discharge pipe thermistor is used to control the discharge pipe.
If the temperature of discharge pipe (used in place of the inner temperature of the
compressor) rises abnormally, the operating frequency drops or the operation must be
halted.
2. The discharge pipe thermistor is used for detecting the discharge thermistor disconnected.
A
B
Compressor
(R3078)
Electrontic
expansion valve
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...