Si21-205
Troubleshooting for Outdoor Unit (25/35 class)
Troubleshooting
191
6.15.7 Outdoor Unit Fan System Check (With AC Motor)
Check No.9
Check the
fan motor lead wire
connector for secure
connection.
Abnormal
YES
NO
NO
Continuity
Are the
resistance at connector
leads
∞
? 1. red - black,
2. white - black
Check the fan
capacitor for continuity.
Does the outdoor
fan rotate?
Does
the outdoor unit fan
start just after the power
is turned on?
Check the outdoor fan system.
YES
YES
NO
Normal
No continuity
Repair.
Replace the fan motor.
Replace the fan motor.
Replace the outdoor unit PCB.
The outdoor fan system is
normal.
(R2670)
Содержание Sky Air B-Series R-410A
Страница 7: ...Si21 205 vi Table of Contents ...
Страница 15: ...Models Si21 205 4 Model Name and Power Supply ...
Страница 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Страница 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Страница 77: ...Settings Concerning Maintenance Si21 205 66 Field Setting FHQ B Service monitor LED Capacity setting adaptor ...
Страница 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Страница 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Страница 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Страница 246: ...Si21 205 FFQ25 35 50 60BV1B Removal Procedure 235 4 Remove the horizontal vane Step Procedure Points S2646 ...
Страница 283: ...Outdoor Unit 25 35 class Si21 205 272 Removal Procedure 2 Slide the MID upward and release Step Procedure Points ...
Страница 285: ...Outdoor Unit 25 35 class Si21 205 274 Removal Procedure 4 Remove the fan motor Step Procedure Points ...
Страница 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...