Outline of Control (Indoor Unit)
SiUS341615E
75
Functions and Control
8.3
Remote Controller Thermistor
Temperature is controlled by both the remote controller thermistor and suction air thermistor for the
indoor unit. (This is however limited to when the field setting for the remote controller thermistor is
set to Use.)
Note:
When outdoor air is introduced to the air-conditioner with mixed into indoor air, the room
temperature may fail to be set temperature, since TS and TH1 do not enter the area of “use range
of remote control thermistor.” In such a case, put the remote sensor (optional accessory) in your
room, and use it with setting “do not use remote control thermostat.”
∗
FXTQ-TA models do not have this control because they do not have suction air thermistor. The
thermistor is selectable manually when remote sensor (optional accessory) is installed.
Cooling
If there is a significant difference in the set temperature and the suction temperature, fine
adjustment control is carried out using a suction air thermistor, or using the remote controller
thermistor near the position of the user when the suction temperature is near the set temperature.
Assuming the set temperature in the figure above is 24°C (75°F), and the suction
temperature has changed from 18°C (64°F) to 30°C (86°F) (A
→
F):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat is off.)
Suction air thermistor is used for temperatures from 18°C (64°F) to 23°C (73°F) (A
→
C).
Remote controller thermistor is used for temperatures from 23°C (73°F) to 27°C (81°F) (C
→
E).
Suction air thermistor is used for temperatures from 27°C (81°F) to 30°C (86°F) (E
→
F).
Assuming suction temperature has changed from 30
°
C (86°F) to 18
°
C (64°F) (F
→
A):
Suction air thermistor is used for temperatures from 30°C (86°F) to 25°C (77°F) (F
→
D).
Remote controller thermistor is used for temperatures from 25°C (77°F) to 21°C (70°F) (D
→
B).
Suction air thermistor is used for temperatures from 21°C (70°F) to 18°C (64°F) (B
→
A).
Set temperature
(Ts)
32
30
28
26
24
22
20
18
16
˚C
˚C
TH1 = Ts – 1
TH1 = Ts + 1
TH1 = Ts + 3
TH1 = Ts – 3
A
B
C
D
E
F
12
14 16 18 20 22 24 26 28 30 32 34
Range in which remote controller
thermistor can be used
Range in which
suction air thermistor
can be used
Suction temperature (TH1)
Differential
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...