Field Settings for Outdoor Unit
SiUS341615E
139
Field Settings
Error code
Description of error
Upper code
Lower code
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
U7
-
1
Error when external control adaptor for outdoor unit is installed
U
7
-
0
1
-
2
Alarm when external control adaptor for outdoor unit is installed
-
0
2
-
3
Transmission error between master and slave 1 units
-
0
3
-
4
Transmission error between master and slave 2 units
-
0
4
-
5
Multi system error
-
0
5
-
6
Error in address settings of slave 1 and 2
-
0
6
-
7
Connection of four or more outdoor units in the same system
-
0
7
-
11
Error in indoor unit connection capacity for test operation
-
1
1
U9
-
1
Other indoor units abnormality
U
9
-
0
1
UA
-
17
Connection of excessive indoor units
U
A
-
1
7
-
18
Connection of wrong models of indoor units
-
1
8
-
20
Improper combination of outdoor units
-
2
0
-
21
Connection error
-
2
1
-
29
Branch selector BSVQ-P connected to heat pump system
-
2
9
-
31
Multi-unit combination error
-
3
1
-
38
Daikin Altherma indoor unit detected
-
3
8
-
39
Other hydrobox type than HXY-A unit detected
-
3
9
-
50
RA connected to BP units and HXY-A unit detected
-
5
0
-
51
Only HXY-a unit(s) connected, minimum 50% DX indoor need
-
5
1
UF
-
1
Wrong wiring check error
U
F
-
0
1
-
5
Defective stop valve for test operation
-
0
5
UH
-
1
Wiring error
U
H
-
0
1
UJ
-
1
Defective active filter (Master)
U
J
-
0
1
-
2
Defective active filter (Slave 1)
-
0
2
-
3
Defective active filter (Slave 2)
-
0
3
Caution Code
Description code
Upper code
SEG
1
SEG
2
SEG
3
P
2
Auto charge more than 5 minutes “t
03
” blinking
P
2
8
Auto charge abnormal end freeze up indoor
P
8
E
Auto charge nearly terminated
P
E
9
Auto charge normal terminated
P
9
E
-
1
Conditions not met to perform leak test
E
-
1
-
2
Indoor air average below 10°C (50°F) for leak test
E
-
2
-
3
Outdoor air below 0°C (32°F) for leak test
E
-
3
-
4
Abnormal low pressure during leak test
E
-
4
-
5
Some indoor not compatible for leak test
E
-
5
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...