Field Settings for Outdoor Unit
SiUS341615E
145
Field Settings
2.6.2 Description Field Settings (mode 2: m2) on Outdoor Unit Main PCB
[2-0]: Cool/Heat selection setting
Cool/Heat selection setting is used in case the optional Cool/Heat selector (KRC19-26A) is used.
Depending on the outdoor unit setup (single outdoor unit setup or multi outdoor unit setup), the correct
setting should be chosen. More details on how to use the Cool/Heat selector option can be found in the
manual of the Cool/Heat selector.
Default value: 0.
0: Each individual outdoor unit can select Cool/Heat operation (by Cool/Heat selector if installed), or by
defining master indoor user interface (see setting [2-83])
1: Master unit decides Cool/Heat operation when outdoor units are connected in multiple system
combination
2: Sub unit for Cool/Heat operation when outdoor units are connected in multiple system combination
[2-1]: Cool/heat unified address
Address for cool/heat unified operation.
When multiple heat pump systems need to change over together between cooling and heating (example
multiple systems serve indoor units in landscape area). Per zone the optional PCB DTA104A61/62 needs
to be installed. Recommended location is in one of the
VRV
indoor units belonging to the system that will
be set as “Master cool/heat unit” (field setting 2-0-1).
The address set to the multiple systems need to operate as a zone, should be same as the address set by
the DIP switches on the related optional PCB DTA104A61/62.
Default value: 0.
Field setting: 1-31.
The source for cool/heat selection can be:
Indoor unit: when outdoor unit DIP switch DS1-1 is at the “OFF” position.
Cool/heat switch: set DIP switch DS1-1 on outdoor unit PCB to “ON”. Operation mode according to
connections A-B-C to optional PCB “BRP2A81”.
[2-2]: Low noise/demand address
Address for low noise/demand operation.
1
or more systems (maximum 10 systems wired by “F1F2 OUT/D”) can operate use the LNO (Low Noise
Operation) or/and the DE (Demand Control) by instruction of field supplied input to optional PCB
DTA104A61/62.
To link the system to the corresponding DTA104A61/62, set the address same as the DIP switches
position on the related optional PCB DTA104A61/62.
Ensure that also field setting 2-12-1 is set to enable input from optional PCB DTA104A61/62.
External
control adaptor
for outdoor unit
No.0
Outdoor
unit group
master No.0
Outdoor
unit group
slave No.0
Outdoor
unit group
slave No.0
Outdoor
unit group
master No.2
Outdoor
unit group
slave No.2
Outdoor
unit group
slave No.2
Outdoor
unit group
master No.1
Outdoor
unit group
slave No.1
Outdoor
unit group
master No.3
Outdoor
unit group
slave No.3
External
control adaptor
for outdoor unit
No.1
External
control adaptor
for outdoor unit
No.2
External
control adaptor
for outdoor unit
No.3
DS2, DS1
DS2, DS1
DS2, DS1
DS2, DS1
C/H group address
C/H group address
C/H group address
C/H group address
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...