Outline of Control (Indoor Unit)
Functions and Control
94
8.15.3 Economizer
When indoor and outdoor air temperatures are reversed, the compressor is stopped to let in the
outdoor air to save energy.
This operation is called economizer operation, and the equipment to detect indoor and outdoor air
temperatures and open and close the damper to perform this operation is called an economizer.
The economizer detects indoor and outdoor air temperatures, informs the air conditioner that the
economizer operation is ready, and opens and closes the damper.
The indoor unit stops the outdoor unit when it receives a signal from the economizer and performs
air supply operation.
When the indoor air temperature is cooled down sufficiently by the economizer operation, and it is
no longer necessary (thermostat OFF), the indoor unit outputs a signal to the economizer to close
the damper.
Thermostat ON signal
Operation
Indoor unit ON signal
∗
1. Thermostat ON signal: A signal to turn ON the indoor unit thermostat and allow the economizer
to open the damper.
It turns ON the relay on the X2M-ECONOMIZER2 on the PCB.
∗
2. External input ON is an input signal to the X1M-ECONOMIZER1 terminal on the PCB.
∗
3. Refer to Optional Kit Setting (UV lamp + Humi Economizer) (for FXTQ-TA model) on page 113.
∗
4. Remote control ON signal: Contact output which shows the operating status of the indoor unit.
This signal turns on the relay X2M-CONTROL ON/OFF on the PCB.
&
Elimination of others
Stop the thermostat ON signal (
∗
1)
to the economizer.
Transfer the thermostat ON signal (
∗
1) to
the economizer.
•
Cooling mode
•
When the thermostat is ON
&
•
Cooling mode
•
When the thermostat is ON
•
External output: ON (
∗
2)
OR
•
Tcon
≤
Ts’ continues for 1
minute
•
Economizer set time (
∗
3):
Free cooling only
&
•
Economizer set time (
∗
3)
≠
Free cooling only
•
Thermostat ON continues for
the economizer set time (
∗
3)
•
Air conditioner operation is
stopped.
•
The remote controller indicates
cooling operation.
•
The fan tap follows the remote
controller.
•
Air conditioner operation is
started.
•
The remote controller
indicates cooling operation.
•
The fan tap follows the
remote controller.
Normal operation
Elimination
of others
Free cooling
Free cooling & Mech Cooling
Remote control ON
Remote control OFF
Stop indoor unit ON signal (
∗
4)
to the economizer.
Transfer indoor unit ON signal (
∗
4) to the
economizer.
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...