Field Settings for Outdoor Unit
SiUS341615E
131
Field Settings
Error code
Description of error
Upper code
Lower code
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
E1
-
1
Outdoor unit PCB error
E
1
-
0
1
-
2
Defective outdoor unit PCB
-
0
2
E2
-
1
Ground leakage detection error – Master unit
E
2
-
0
1
-
2
Ground leakage detection error – Slave unit 1
-
0
2
-
3
Ground leakage detection error – Slave unit 2
-
0
3
-
6
Missing of ground leakage detection core – Master unit
-
0
6
-
7
Missing of ground leakage detection core – Slave unit 1
-
0
7
-
8
Missing of ground leakage detection core – Slave unit 2
-
0
8
E3
-
1
Actuation of high pressure switch – Master unit
E
3
-
0
1
-
2
High pressure - refrigerant overcharge or closed stop valve – Master unit
-
0
2
-
3
Actuation of high pressure switch – Slave unit 1
-
0
3
-
4
High pressure - refrigerant overcharge or closed stop valve – Slave unit 1
-
0
4
-
5
Actuation of high pressure switch – Slave unit 2
-
0
5
-
6
High pressure - refrigerant overcharge or closed stop valve – Slave unit 2
-
0
6
-
13
Liquid stop valve check error – Master unit
-
1
3
-
14
Liquid stop valve check error – Slave unit 1
-
1
4
-
15
Liquid stop valve check error – Slave unit 2
-
1
5
-
18
Overall retry of high pressure switch
-
1
8
E4
-
1
Low pressure sensor error – Master unit
E
4
-
0
1
-
2
Low pressure sensor error – Slave unit 1
-
0
2
-
3
Low pressure sensor error – Slave unit 2
-
0
3
E5
-
1
Inverter compressor 1 lock – Master unit
E
5
-
0
1
-
2
Inverter compressor 1 lock – Slave unit 1
-
0
2
-
3
Inverter compressor 1 lock – Slave unit 2
-
0
3
-
7
Inverter compressor 2 lock – Master unit
-
0
7
-
8
Inverter compressor 2 lock – Slave unit 1
-
0
8
-
9
Inverter compressor 2 lock – Slave unit 2
-
0
9
E7
-
1
Fan motor 1 lock – Master unit
E
7
-
0
1
-
2
Fan motor 2 lock – Master unit
-
0
2
-
5
Fan motor 1 momentary overcurrent – Master unit
-
0
5
-
6
Fan motor 2 momentary overcurrent – Master unit
-
0
6
-
9
Fan motor 1 IPM error – Master unit
-
0
9
-
10
Fan motor 2 IPM error – Master unit
-
0
9
-
13
Fan motor 1 lock – Slave unit 1
-
1
3
-
14
Fan motor 2 lock – Slave unit 1
-
1
4
-
17
Fan motor 1 momentary overcurrent – Slave unit 1
-
1
7
-
18
Fan motor 2 momentary overcurrent – Slave unit 1
-
1
8
-
21
Fan motor 1 IPM error – Slave unit 1
-
2
1
-
22
Fan motor 2 IPM error – Slave unit 1
-
2
2
-
25
Fan motor 1 lock – Slave unit 2
-
2
5
-
26
Fan motor 1 lock – Slave unit 2
-
2
6
-
29
Fan motor 1 momentary overcurrent – Slave unit 2
-
2
9
-
30
Fan motor 2 momentary overcurrent – Slave unit 2
-
3
0
-
33
Fan motor 1 IPM error – Slave unit 2
-
3
3
-
34
Fan motor 2 IPM error – Slave unit 2
-
3
4
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...