Field Settings for Outdoor Unit
SiUS341615E
149
Field Settings
Next time graph shows the different steps during the power transistor check mode.
Switching sequence during power transistor check mode:
[2-29]: Capacity priority
When the night-time low noise operation is in use, performance of system might drop because airflow rate
of outdoor unit is reduced.
Default value: 0. Capacity priority cannot be used.
Field setting 1: Capacity priority can temporary cancel the night-time low noise operation. Capacity priority
can be initiated when certain operation parameters approach the safety setting:
Raise in high pressure during cooling.
Drop in low pressure during heating.
Raise of discharge pipe temperature.
Raise of inverter current.
Raise of fin temperature inverter PCB.
Power transistor check mode RXYQ-TA
disconnect fasten U/V/W from compressor!
step1:
mode 2
code 28
set 01 02
"Return" 2x
step 2:
mode 2 - code 28
set 02 01+"Return
2x OR exit mode 2
("mode" button)
Check
1
Check
2
Check
3
Check 5
Magnet
sw.
K1M
ON
Magnet sw.
K1M OFF
Voltage
output
U-V-W
Voltage
output
U-V-W
Frequency: 10 Hz
Frequency: 240 Hz
±100
VAC
note
∗
±60 VAC
note
∗
±170
VAC
note
∗
±6 sec
±3 sec
±3 sec
±30 sec
Check 1
: AC power input (connector X10A on A2P: inverter compressor) 380-415 V
unbalance max.2%.
Check 2
: relay "K1M" on inverter PCB switches : check DC voltage on P&N increase to
±500 VDC.
Check 3
: DC = 1.42 x VAC power supply L1-L3 : check at connector X3A (8-12 HP), or
X5,6A (14-20 HP).
Check 4
: AC UVW 10 Hz intermediate : check difference within 10 V (at fasten U/V/W)
Check 5
: AC UVW 240 Hz continuous output while voltage drop (discharge capacitors DC)
check difference between UVW within 10 V. 2 LEDs (V phase) brightness reduce
till of.
∗
note : actual voltage value depends on meter characteristics
Check 4
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...