SiUS341615E
Field Settings for Outdoor Unit
Field Settings
152
[2-37]: Heat pump lockout 2
Heat pump is locked out when this setting and an external input to ABC terminal are made.
Automatic lockout
When this setting is made, the auto-backup function will automatically be activated. This will allow the
auxiliary or secondary heat source to be automatically energized in the event of a system failure related to
outdoor units.
∗
1.
For a heater which does not need airflow
∗
2
.
Depends on the indoor unit field setting 12(22)-3.
[2-38]: Emergency operation “Master”
To disable permanent compressor operation: in case of single module or “Master” unit of a multi outdoor
system, this setting allows:
Default value: 0. Compressor operation enabled.
Field setting:
Set 1: inverter 1 compressor is disabled.
Set 2: inverter 2 compressor is disabled. Only to make in case of 12/14 ton.
Note that compressor 2 is left side located.
Set 3: all compressors in this master module are disabled permanent.
[2-39]: Emergency operation “Slave 1”
To disable permanent compressor operation of “Slave 1” unit of a multi outdoor system (RXYQ-TA):
Default value: 0. Compressor operation enabled.
Field setting:
Set 1: inverter 1 compressor is disabled.
Set 2: inverter 2 compressor is disabled. Only to make in case of 12/14 ton. Note that compressor 2 is
left side located.
Set 3: all compressors in this master module are disabled permanent.
Value
[2-37]
Heat pump lockout 2
0 (default)
OFF
1
Mode 1
2
Mode 2
3
Mode 3
4
Mode 4
5
Mode 5
6
Mode 6
Mode
Description
Actions
Field setting
Shorted
between
Heating Thermo-on Heating Thermo-off
Heater
Fan
Heater
Fan
Mode 1
Lockout is controlled by an
external input to ABC terminal
2-37: Mode 1
A-C
ON
ON (H/L)
OFF
LL (
∗
2)
B-C
OFF
Mode 2
(
∗
1)
2-37: Mode 2
A-C
LL
LL (
∗
2)
B-C
OFF
OFF
Mode 3
Lockout is controlled by the
outdoor temperature and
setpoint which is configured by
the setting [2-94] and [2-95]
2-37: Mode 3
Same as 2-37: Mode 1, A-C shorted
Mode 4
2-37: Mode 4
Same as 2-37: Mode 1, B-C shorted
Mode 5
2-37: Mode 5
Same as 2-37: Mode 2, A-C shorted
Mode 6
2-37: Mode 6
Same as 2-37: Mode 2, B-C shorted
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...