Troubleshooting by Error Code
SiUS341615E
175
Service Diagnosis
3.1.2 External Protection Device Abnormality (FXTQ-TA Only)
Error Code
A0-01
Applicable
Models
FXTQ-TA
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals.
Supposed
Causes
Actuation of external protection device
Defective indoor unit PCB
Indoor unit fuse blown
Troubleshooting
Fuse (F1U)
is blown.
Ex
ternal
protection device
is connected to TB4 and
TB5 of the indoor unit
terminal.
The
external protection
device is opened.
Replace the indoor unit PCB.
Actuation of external protection
device.
Replace the fuse (F1U).
YES
YES
NO
NO
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...