Basic Control
SiUS341615E
59
Functions and Control
5.4
Compressor Step Control
The actual rotation speed per second of the compressor (rps) depends on the type of compressor:
The change of compressor capacity step corresponds to 1 rps / step.
The control can skip an number of steps to reach faster the target saturated temperature.
5.5
Electronic Expansion Valve Control
Electronic expansion valve Y1E
Cooling: electronic expansion valve is used only at fully closed or fully open condition:
Compressor(s) OFF: fully closed (0 pulse)
Compressor ON:
Fully open (3,000 pulses): if level difference outdoor above indoor units within 50 m (164 ft)
(field setting 2-49-0).
Limited open: if level difference outdoor maximum 90 m (295 ft) above indoor units (field setting 2-49-1).
Heating: electronic expansion valve is used in PID control suction superheat:
Compressor(s) OFF: fully closed (0 pulse)
Compressor ON:
At startup: closed (check suction pressure drops)
Modulated opening by:
Suction superheat = accumulator inlet temperature – evaporating temperature.
Discharge superheat = discharge pipe temperature – condensing temperature.
Preventive change when compressor capacity step changes.
Limited opening when condensing temperate exceeds target condensing.
Compressor
Actual rotation speed
TAYDU
TATJU
72
96/120
144/168
72
96/120
144/168
JT1GCVDWYR
rps = frequency/2
z
–
zz
–
–
–
JT15JBVDWYR
rps = frequency/3
–
z
–
–
–
–
JT100GCVDKW
rps = frequency/2
–
–
–
z
–
zz
JT150JBVDW
rps = frequency/3
–
–
–
–
z
–
0
Inverter
compressor
Main
Y1E
0 Hz
3,000
Pulses
Inverter
compressor
Main
Y1E
0 Hz
0
3,000
Pulses
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...