SiUS341615E
Service Mode
Remote Controller
48
∗
1. (For FXTQ-TA models)
The actual fan speed is converted into the fan tap to be displayed. Therefore, if the fan speed is changed by
controls or external factors, the airflow rate set with the remote controller may differ from the fan tap display.
∗
2. (For FXTQ-TA models)
0 rpm
is displayed even if the fan is rotating.
∗
3. (For FXTQ-TA models)
The ON/OFF status of the humidifier connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB is
not displayed. The ON/OFF status of the humidifier connected to the wiring adaptor is displayed.
Indoor Unit Status
10.FLOAT
FLOAT SWITCH ON/OFF
11.T1/T2
T1/T2 input from outside ON/OFF
12.Th1
Suction air thermistor
13.Th2
Heat exchanger liquid pipe thermistor
14.Th3
Heat exchanger gas pipe thermistor
15.Th4
Discharge air thermistor
16.Th5
—
17.Th6
—
Outdoor Unit Status
1. Unit No.
Select the Unit No. you want to check.
2. FAN step
Fan tap
3. COMP
Compressor power supply frequency (Hz)
4. EV1
Degree that electronic expansion valve is open (pulse)
5. SV1
Solenoid valve ON/OFF
6. Th1
—
7. Th2
—
8. Th3
—
9. Th4
—
10.Th5
—
11.Th6
—
Forced Defrost
1. Forced defrost ON
Enables the forced defrost operation.
2. Forced defrost OFF
Disables the forced defrost operation.
Error Display
1. Display Error ON
Displays the error on the screen.
2. Display Error OFF
Displays neither errors nor warnings.
3. Display Warning ON
Displays a warning on the screen if an error occurs.
4. Display Warning OFF
No warning is displayed.
Swap Unit No.
1. Current Unit No.
A unit No. can be transferred to another.
2. Transfer Unit No.
Addressed Sensor
Value
Unit No.: 0 - 15
Select the Unit No. you want to check.
Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
Remote controller thermistor (°C)
Suction air thermistor (°C)
Heat exchanger liquid pipe thermistor (°C)
Heat exchanger gas pipe thermistor (°C)
Indoor unit address No.
Outdoor unit address No.
Branch selector unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
Data
The corresponding data will be displayed, based on the Unit No.
and Code selected.
Maintenance Menu
Item 2
Remarks
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...