Troubleshooting by Error Code
SiUS341615E
249
Service Diagnosis
3.48 Inverter Compressor Startup Abnormality
Error Code
L9
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect error according to the signal waveform of compressor.
Error Decision
Conditions
When compressor startup operation has not been completed.
Supposed
Causes
The stop valve is not opened
Defective compressor
Error in wire connections to compressor
Large differential pressure before compressor startup
Defective inverter PCB