Field Setting from Remote Controller
SiUS341615E
101
Field Settings
Note :
1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside
parentheses, you can also set by each individual unit. Setting changes however cannot be checked except in
the individual mode for those in parentheses.
∗
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they cannot be set
individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the indoor unit is
not equipped with.
4.
88
or
Checking the connection. Please stand by.
may be displayed to indicate the remote controller is
resetting when returning to the normal mode.
∗
5. If the setting mode to “Equipped”, energy recovery ventilator fan conducts the fan residual operation by
linking to indoor unit.
∗
6. Only for FXTQ-TA models
∗
7. Only for FXTQ-TA, FXDQ-M models
∗
8. If the airflow setting when thermostat is OFF is set to OFF (12(22)-3-03, 12(22)-6-03), the air in the indoor
unit will be stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10(20)-2 to
03
(only remote controller
thermistor).
∗
9. Only for FXFQ-T and FXUQ-P sensing models
Mode
No.
(
∗
2)
First
Code
No.
Setting Contents
Second Code No.
01
02
03
04
13(23)
0
Setting of airflow rate
Standard
High ceiling 1
High ceiling 2
—
1
Airflow direction setting
(Set when a blocking pad kit has been installed.)
F (4 directions)
T (3 directions)
W
(2 directions)
—
2
Swing pattern settings
All direction
synchronized swing
—
Facing swing
—
3
Operation of downward flow flap
Equipped
Not equipped
—
—
4
Setting of airflow direction adjustment range
Draft prevention
Standard
Ceiling soiling
prevention
—
5
Setting of static pressure selection
Standard
High static pressure
—
—
6
External static pressure settings
Refer to page 112 for detail.
14
(24)
4 (*6)
Optional kit setting (UV lamp + humi
economizer)
Refer to page 113 for details.
5 (*6)
Residential dry
Set temperature:
room temperature
Set temperature:
same as cooling set
temperature
—
—
15(25)
0
Drain pump operation settings
—
ON
OFF
—
1
Humidification when heating thermostat is OFF
Not equipped
Equipped
—
—
2
Setting of direct duct connection
(when the indoor unit and energy recovery
ventilator unit are connected by duct directly.)
(
∗
5)
Not equipped
Equipped
—
—
3
Interlocked operation between humidifier and
drain pump
Not equipped
Equipped
—
—
5
Individual setting of ventilation
Not equipped
Equipped
—
—
1b (2b)
3
Display of contact center
Displayed
Not displayed
—
—
4
Display of error codes on the remote controller
—
Two-digit display
—
Four-digit
display
12
Key-lock pattern settings
No operation
allowed (Cancel
procedure is
displayed.)
No operation
allowed (Cancel
procedure is not
displayed.)
No menu
operation is
allowed
(Cancel
procedure is
displayed.)
No menu
operation is
allowed any
time.
14
Setting "restricted / permitted" of airflow block
Refer to page 115 for detail.
1c (2c)
0
Room temperature display
Room temperature
is not displayed
Room temperature
is displayed
—
—
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...