SiUS341615E
Field Setting from Remote Controller
Field Settings
110
Thermostat Switching
Differential value during thermostat ON/OFF control can be changed.
Airflow Setting when Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
∗
When thermostat OFF airflow volume up mode is used, careful consideration is required before deciding
installation location.
Setting of Operation Mode to AUTO
This setting makes it possible to change differential values for mode selection while in automatic operation mode.
The automatic operation mode setting is made by the use of the "Operation Mode Selector" button.
Auto Restart after Power Failure Reset
For the air conditioners with no setting for the function, the units will be left in the stop condition when the power
supply is reset automatically after power failure reset or the main power supply is turned ON again after once
turned OFF. However, for the air conditioners with the setting (same as factory setting), the units may start
automatically after power failure reset or the main power supply turned ON again (return to the same operation
condition as that of before power failure).
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power failure reset”,
utmost care should be paid for the occurrence of the following situation.
Airflow when Cooling Thermostat is OFF
This is used to set airflow to "LL airflow" when cooling thermostat is OFF.
Mode No.
First Code No.
Second Code No.
Contents
12(22)
2
01
1°C (1.8°F)
02
0.5°C (0.9°F)
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
3
01
LL tap
02
Set fan speed
03
OFF
Mode No.
First Code No.
Second Code No.
01
02
03
04
05
06
07
08
12 (22)
4
0°C
(0°F)
1°C
(1.8°F)
2°C
(3.6°F)
3°C
(5.4°F)
4°C
(7.2°F)
5°C
(9.0°F)
6°C
(10.8°F)
7°C
(12.6°F)
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
5
01
Not equipped
02
Equipped
Caution The air conditioner starts operation suddenly after power failure reset or
when the main power supply is turned on again. Consequently, the user
might be surprised and wonder why this has happened. In service work, for
example, turning off the main power switch while the unit is in operation,
and turning on the switch again after the work is completed start unit
operation (the fan rotates).
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
6
01
LL tap
02
Set fan speed
03
OFF
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...