SiMT041311E
Control Specification
Function and Control
48
2.3
Discharge Pipe Temperature Control
Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to
keep the discharge pipe temperature from rising further.
Detail
Correction value (a) = correction value by operation frequency (b)
+ correction value by outdoor temperature (c)
Correction value by operation frequency (b)
Correction value by outdoor temperature (c)
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is cancelled.
105 – correction value (a)
115 – correction value (a)
103 – correction value (a)
97 – correction value (a)
85 – correction value (a)
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
(R19672)
Discharge pipe
temperature (˚C)
Correction value (b) = 12 deg
Correction value (b) = 0 deg
Correction value (b) = 20 deg
50 Hz
21 Hz
45 Hz
16 Hz
Operation frequency
(R19673)
Correction value (c) = 0 deg
Correction value (c) = 5 deg
– 10˚C
– 9˚C
Outdoor temperature
(R13909)