Troubleshooting
SiMT041311E
157
Service Diagnosis
Troubleshooting
In case of H9, J3, J6, J8
Check No.01
Refer to P.181
H9
: Outdoor temperature thermistor
J3
: Discharge pipe thermistor
J6
: Outdoor heat exchanger thermistor
J8
: Liquid pipe thermistor
(R19731)
Caution
NO
YES
YES
NO
NO
YES
Turn on the power again.
Normal?
Reconnect the connector
and thermistor.
J3
error: the discharge
pipe temperature is
lower than the heat
exchanger temperature.
Replace the thermistor.
Cooling: Outdoor heat
exchanger
temperature
Heating: Indoor heat
exchanger
temperature
Replace the indoor heat
exchanger thermistor.
Replace the outdoor unit
PCB.
Error displayed
again on remote
controller?
Indoor heat
exchanger thermistor
functioning?
Check No. 01
Check the thermistor resistance
value.
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in the
heating operation.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.