Troubleshooting
Service Diagnosis
156
2.26 Thermistor or Related Abnormality (Outdoor Unit)
Error Code
H9, J3, J6, J8, P4
Method of Error
Detection
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision
Conditions
The thermistor input voltage is 4.98 V and more or 0.02 V and less for 5 seconds with the
power on.
J3
error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Supposed
Causes
Disconnection of the connector for the thermistor
Thermistor corresponding to the error code is defective.
Defective heat exchanger thermistor in the case of
J3
error (outdoor heat exchanger
thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Troubleshooting
In case of P4 (Radiation fin thermistor)
Replace the outdoor unit PCB.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.