Main Functions
SiMT041311E
13
Function and Control
Drawing of
Inverter
The following drawing shows a schematic view of the inverter principle:
Inverter Features
The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor
temperature and cooling / heating load.
Quick heating and quick cooling
The rotation speed of the compressor is increased when starting the heating (or cooling).
This enables to reach the set temperature quickly.
Even during extreme cold weather, the high capacity is achieved. It is maintained even when
the outdoor temperature is 2°C.
Comfortable air conditioning
A fine adjustment is integrated to keep the room temperature constant.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
Frequency Limits
The following functions regulate the minimum and maximum frequency:
Forced Cooling
Operation
Refer to page 192 for details.
Refrigerant circulation rate (high)
high f
low f
freq=variable
Refrigerant circulation rate (low)
high speed
low speed
(R2812)
Amount of heat
exchanged air (large)
freq=
constant
50 Hz
60 Hz
capacity=
variable
Amount of heat
exchanged air (small)
AC
po
w
e
r
DC po
w
er
Amount of heat
exchanged air (large)
Amount of heat
exchanged air (small)
Frequency
Functions
Low
Four way valve operation compensation. Refer to page 46.
High
Compressor protection function. Refer to page 47.
Discharge pipe temperature control. Refer to page 48.
Input current control. Refer to page 49.
Freeze-up protection control. Refer to page 50.
Heating peak-cut control. Refer to page 50.
Defrost control. Refer to page 53.