SiMT041311E
Troubleshooting
Service Diagnosis
146
2.18 DC Fan Lock
Error Code
E7
Method of Error
Detection
An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC.
Error Decision
Conditions
The fan does not start in 60 seconds even when the fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Disconnection of the fan motor
Foreign matters stuck in the fan
Defective fan motor
Fuse for fan motor on the outdoor unit PCB is blown out.
Defective outdoor unit PCB
Troubleshooting
Check No.16
Refer to P.187
(R20202)
Caution
YES
YES
NO
NO
YES
NO
YES
NO
YES
NO
Turn on the power.
Rotate the fan.
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB.
Turn off the power and
reconnect the connector.
Remove the foreign
matters.
Replace the outdoor unit
PCB.
Replace the outdoor fan
motor.
Replace the fuse.
∗
Check the location of the
fuse on the wiring
diagram.
Fan motor connector
disconnected?
Foreign matters in or
around the fan?
Replace the outdoor fan
motor.
Fan rotates
smoothly?
Pulse signal generated?
Fuse for fan motor
on the
outdoor unit PCB
blown out?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.