SiMT041311E
Check
Service Diagnosis
182
3.2
Fan Motor Connector Output Check
Check No.02
1. Check the connection of connector.
2. Turn off the power.
3. Check if the resistances between the phases U - V (pins 1 - 7) and between the phases
V - W (pins 7 - 4) are 45 ~ 65
Ω
respectively.
3.3
Humidity Sensor Check
Check No.07
1. Check the connection of connector.
2. Check the input from the humidity sensor (*1).
3. Change the ambient conditions (*2) and check that the input level changes accordingly.
*1 The voltage value may differ depending on the sensors.
*2 Change the humidity, temperature, airflow rate. To do this, merely breathe upon.