Control Specification
SiUS042113E
66
Part 4 Functions and Control
3.5 Discharge Pipe Temperature Control
Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
the discharge pipe temperature from rising further.
Details
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
(°C)
(°F)
A
118
244
B
108
226
C
103
217
D
97
207
E
85
185
(R25005)
Discharge pipe
temperat
u
re
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
E
A
B
C
D
Содержание FTXM-V Series
Страница 13: ...SiUS042113E Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Страница 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Страница 147: ...SiUS042113E Check Part 6 Service Diagnosis 143 09 12 class 18 24 class 1 2 3 4 Multimeter R24538 1 2 3 4 Multimeter...
Страница 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Страница 165: ...SiUS042113E Piping Diagrams Part 8 Appendix 161 1 2 Outdoor Unit RXM09 12VVJU RXM18VVJU 3D131979 3D132216...
Страница 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Страница 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...