Control Specification
SiUS042113E
70
Part 4 Functions and Control
3.10 Outdoor Fan Control
1.
Fan ON control to cool down the electrical box
The outdoor fan is turned ON when the electrical box temperature is high while the compressor
is OFF.
2.
Fan OFF control during defrosting
The outdoor fan is turned OFF while defrosting.
3.
Fan OFF delay when stopped
The outdoor fan is turned OFF 60 ~ 70 seconds after the compressor stops.
4.
Fan speed control for pressure difference upkeep
The rotation speed of the outdoor fan is controlled for keeping the pressure difference during
cooling operation with low outdoor temperature.
When the pressure difference is low, the rotation speed of the outdoor fan is reduced.
When the pressure difference is high, the rotation speed of the outdoor fan is controlled as
well as normal operation.
5.
Fan speed control during forced operation
The outdoor fan is controlled as well as normal operation during forced operation.
6.
Fan speed control during POWERFUL operation
The rotation speed of the outdoor fan is increased during POWERFUL operation.
7.
Fan speed control during indoor/outdoor unit quiet operation
The rotation speed of the outdoor fan is reduced by the command of the indoor/outdoor unit
quiet operation.
8.
Fan ON/OFF control when operation (cooling, heating, dry) starts/stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF when
the operation stops.
3.11 Liquid Compression Protection Function
Outline
The compressor stops according to the outdoor temperature for protection.
Details
Operation stops depending on the outdoor temperature.
The compressor turns off under the conditions that the system is in cooling operation and the
outdoor temperature is below 0°C (32°F).
Содержание FTXM-V Series
Страница 13: ...SiUS042113E Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Страница 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Страница 147: ...SiUS042113E Check Part 6 Service Diagnosis 143 09 12 class 18 24 class 1 2 3 4 Multimeter R24538 1 2 3 4 Multimeter...
Страница 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Страница 165: ...SiUS042113E Piping Diagrams Part 8 Appendix 161 1 2 Outdoor Unit RXM09 12VVJU RXM18VVJU 3D131979 3D132216...
Страница 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Страница 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...