SiUS042113E
Control Specification
Part 4 Functions and Control
71
3.12 Defrost Control
Outline
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat
exchanger temperature must be more than a certain value to finish defrosting.
Details
Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than
A
minutes (depending on the duration of the previous defrost control) of accumulated
time have passed after the start of the operation, or ending the previous defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature. (
B
°C)
09/12 class
18/24 class
A
(minutes)
15 ~ 25
48
B
(°C)
6 ~ 11.5
4 ~ 12
(°F)
43 ~ 53
39 ~ 54
C
(Hz)
48
48
D
(Hz)
80
62
E
(seconds)
35
60
F
(seconds)
60
60
G
(seconds)
120 ~ 570
120 ~ 460
H
(seconds)
75
60
J
(pulse)
470
450
K
(pulse)
400 ~ 444
490
L
(pulse)
402
400
Freq
u
ency
Compressor
Fo
u
r way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz
0 Hz
C
Hz
D
Hz
5 ~ 8 sec.
PI control
5 ~ 8 sec.
H
sec.
(R21278)
E
sec.
F
sec.
G
sec.
K
p
u
lse zone
Electronic
expansion valve
opening
Normal
control
J
p
u
lse
zone
L
p
u
lse
zone
Starting
control
Содержание FTXM-V Series
Страница 13: ...SiUS042113E Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Страница 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Страница 147: ...SiUS042113E Check Part 6 Service Diagnosis 143 09 12 class 18 24 class 1 2 3 4 Multimeter R24538 1 2 3 4 Multimeter...
Страница 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Страница 165: ...SiUS042113E Piping Diagrams Part 8 Appendix 161 1 2 Outdoor Unit RXM09 12VVJU RXM18VVJU 3D131979 3D132216...
Страница 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Страница 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...