38
Part 4 Functions and Control
Note(s)
Note(s)
3. Airflow direction in 2-area INTELLIGENT EYE operation
Detection method: The opposite area of detected area is set as the target direction.
1. Human detection signal ON in both areas A and B: Shift the airflow direction to area B (left side)
2. Human detection signal ON in area A: Shift the airflow direction to area B (left side)
3. Human detection signal ON in area B: Shift the airflow direction to area A (right side)
4. Human detection signal OFF in both areas A and B: No change
When the human detection signal is OFF for 20 minutes in both areas A and B, the unit starts
energy saving operation.
For dry operation, the temperature cannot be set with a remote controller, but the target
temperature is shifted internally.
Comfort/Focus
Airflow
Depending on the settings, you can select the airflow control whether blowing directly toward
(Focus) or away from (Comfort) the people.
R4003787
Notes on energy saving operation
If no presence detected in the room for 20 minutes, the energy saving operation will start, and
the INTELLIGENT EYE lamp goes off.
If human movement is detected again, the INTELLIGENT EYE lamp lights up and energy
saving operation terminates.
This operation changes the temperature by –3.6°F (–2.0°C) in HEAT / +3.6°F (+2.0°C) in COOL
/ +3.6°F (+2.0°C) in DRY operation from the set temperature.
When the room temperature exceeds 86°F (30.0°C), the operation changes the temperature by
+1.8°F (+1.0°C) in COOL / +1.8°F (+1.0°C) in DRY operation from the set temperature.
This operation decreases the airflow rate slightly in FAN operation only.
Top view
Wall
Indoor
u
nit
Area A
Area B
Left
Right
H
u
man
(R3853)
[Example]
A person is detected in
area 1.
A person is detected in
area 2.
People are detected in
both areas.
No people are detected in
the areas.
Area 1
Area 2
Area 1
Area 2
Area 1
Area 2
When INTELLIGENT EYE
operation is used, the unit will
not blow air directly at people
(only in their general direction).
The air conditioner will switch
to energy-saving mode after
20 minutes.
Area 1
Area 2
Area 1
Area 2
Содержание FTXM-V Series
Страница 13: ...SiUS042113E Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Страница 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Страница 147: ...SiUS042113E Check Part 6 Service Diagnosis 143 09 12 class 18 24 class 1 2 3 4 Multimeter R24538 1 2 3 4 Multimeter...
Страница 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Страница 165: ...SiUS042113E Piping Diagrams Part 8 Appendix 161 1 2 Outdoor Unit RXM09 12VVJU RXM18VVJU 3D131979 3D132216...
Страница 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Страница 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...