Part 6 Service Diagnosis
5.13 Capacitor Voltage Check
Check No.21
Before this check, turn the circuit breaker off and wait for 10 minutes for prevention of electric
shock.
09/12 class
R6000792
To prevent electrical shock, use a multimeter to check that the voltage between DC_P2 (+)
and DC_N2 (–) is 50 V or less.
18/24 class
R6000790
To prevent an electrical shock, use a multimeter to check that the voltage between FU2 and
DC– is 50 V or less.
The surface of the test points (FU2, DC–) may be covered with the coating. Be sure to make
firm contact between the multimeter probes and the test points.
FU2
DC–
Coating
PCB
Multimeter probe