Main Functions
SiUS042113E
40
Part 4 Functions and Control
1.12 INTELLIGENT EYE Operation
Applicable
Models
FTXM18/24VVJU
Outline
This function detects the presence of humans in the room with a motion sensor and reduces the
capacity when there is nobody in the room in order to save electricity.
Details
1. INTELLIGENT EYE detection method
R4003811
The motion sensor detects human motion by receiving infrared rays and sends the pulse wave
output.
The microcomputer in the indoor unit carries out a sampling every 20 msec. If the motion sensor
detects 10 times or more of the wave output in one second in total, and the High signal
continues for 2 sec., the microcomputer judges humans are in the room as the human detection
signal is ON.
2. Motions (in cooling)
In FAN operation, the fan speed is reduced by 60 rpm when no one is in the area.
When there is no signal from the motion sensor in 20 minutes, the microcomputer judges that
nobody is in the room and operates the unit at a temperature shifted from the target
temperature. (Cooling/Dry: 1 ~ 2°C (1.8 ~ 3.6°F) higher, Heating: 2°C (3.6°F) lower, Auto:
according to the operation mode at that time)
1 sec.
Sampling (20 msec.)
High
Low
ON
OFF
High
Low
(Condition of 10 times or more output)
Human motion
2 sec.
If the detection signal (High) continues for 2 sec. or more,
the microcomputer judges humans are in the room.
Detection signal
from the motion
sensor
Human detection
signal
Motion sensor
output
If the motion sensor detects the outputs
10 times/sec. or more, the microcomputer
judges the detection signal from the
motion sensor is High.
ON
OFF
Reset
Reset
Reset
20 min.
1 ~ 2°C (1.8 ~ 3.6 °F)
ON
OFF
ON
OFF
Operation
OFF
Fan speed (
#
)
Set speed
Set speed
Target temperat
u
re
(R23920)
Remote controller
Sensor
b
u
tton
H
u
man detection
signal
↑
↑
60 rpm
↑
within
20 min.
within
20 min.
within
20 min.
Содержание FTXM-V Series
Страница 13: ...SiUS042113E Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Страница 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Страница 147: ...SiUS042113E Check Part 6 Service Diagnosis 143 09 12 class 18 24 class 1 2 3 4 Multimeter R24538 1 2 3 4 Multimeter...
Страница 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Страница 165: ...SiUS042113E Piping Diagrams Part 8 Appendix 161 1 2 Outdoor Unit RXM09 12VVJU RXM18VVJU 3D131979 3D132216...
Страница 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Страница 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...