Part 4 Functions and Control
Notes
1.13 POWERFUL Operation
Outline
In order to exploit the cooling and heating capacity to full extent, the air conditioner can be operated
by increasing the indoor fan rotating speed and the compressor frequency.
Details
When
POWERFUL
button is pressed, the fan speed and target temperature are converted to the
following states for 20 minutes.
A
= 70 ~ 80 rpm
Ex: POWERFUL operation in cooling
POWERFUL operation cannot be used together with ECONO, COMFORT AIRFLOW or
OUTDOOR UNIT QUIET operation.
Operation mode
Fan speed
Target temperature
COOL
H tap +
A
rpm
18°C (64.4°F)
DRY
Dry rotating speed +
A
rpm
Lowered by 2.5°C (4.5°F)
HEAT
H tap +
A
rpm
31°C (87.8°F)
FAN
H tap +
A
rpm
—
AUTO
Same as cooling/heating in
POWERFUL operation
The target temperature is kept
unchanged.
(R24589)
Target temp.
Fan
A
rpm
H tap
Set tap
20 min
u
tes
Lower limit of cooling
temperat
u
re
Remote controller registers
20 min
u
tes independently.
POWERFUL
ON
POWERFUL
OFF
Ending conditions:
1. Lapse of 20 min
u
tes
2. System operation OFF
3. POWERFUL operation OFF
18°C (64.4°F)
Содержание FTXM-V Series
Страница 13: ...SiUS042113E Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Страница 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Страница 147: ...SiUS042113E Check Part 6 Service Diagnosis 143 09 12 class 18 24 class 1 2 3 4 Multimeter R24538 1 2 3 4 Multimeter...
Страница 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Страница 165: ...SiUS042113E Piping Diagrams Part 8 Appendix 161 1 2 Outdoor Unit RXM09 12VVJU RXM18VVJU 3D131979 3D132216...
Страница 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Страница 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...