System Settings Menu Operation
8.
In the Screen 3 Events on the previous page,
pressing the [Advanced settings] (See
!4
) will
display the Advanced settings screen shown in the
Screen 4 on the left side. The information displayed
in the boxes pointed by
!7
to
@0
is the current
settings of the event.
¡
Operation Mode : In this box, select an operation
mode specified to Zone or
Group. From the pull-down
menu (see
!7
), select either of
Cool / Heat / Auto / Fan /
Dependent / Dry / No change.
Though the operation mode is
set to Dry, some indoor unit with
no change over option will not
be changed to the Dry mode
except in the cooling mode.
* Dependent can be used to order the indoor unit,
without change over option in the VRV, to
perform the temperature control operation other
than the fan operation. When the interlock
condition is met, this indoor unit will operate in
the same operation mode as that of another
indoor unit with change over option. For the
same reason, even if the cooling / heating mode
is set to an indoor unit without change over
option, this unit operates in the same operation
mode as that of another indoor unit with change
over option. For detailed information about the
change over option, please refer to the operation
manual of the air conditioning unit.
¡
Setpoint : In this box, set a temperature of Zone
or Group. Pressing the [Modify] button
(see
!8
) will display the keyboard for
registering a temperature, where you
can input the desired temperature. The
[Disable] button will be shown after
pressing the [Modify] button once to set
a temperature. Pressing the [Disable]
button will cancel the temperature
specified by the Modify operation
described above.
To the HRVs included in the interlock operation
targets, the settings described below can be made.
However, this setting menu will be displayed even
when the HRVs are not included in the targets, but
any settings made in this menu will do nothing.
¡
Ventilation mode : In this box, set the ventilation
mode. From the pull-down
menu (see
!9
), select either of
Automatic / Heat Exchange /
Bypass / No change.
¡
Ventilation amount : In this box, set the ventilation
amount. From the pull-down
menu (see
@0
), select either of
Auto (Normal)/Low (Normal) /
High (Normal) / Auto
(Freshen up) / Low (Freshen
up) / High (Freshen up) / No
change.
When the advanced settings are completed, press
the [OK] button to go back to the Screen 3 shown on
the previous page. Pressing the [OK] buttons in the
Screen 3 and the Screen 2 continuously to go back
to the Screen 1 shown on the previous page.
The next step is to specify a name of the simple
interlock, followed by the validity / invalidity setting.
(Details of these settings will be described in the
next page.)
Screen 4 Advanced settings
17
18
19
20