1.
The
Registered
list
q
shows indoor units
registered in a control group.
The
Unregistered
list
w
shows indoor units
not shown in the
Registered
list
q
.
2.
When adding an indoor unit to a control group,
select a unit to add from the Unregistered list
w
and press [<<] button
e
. (The added unit
is then relocated to the Registered list
q
.)
3.
When deleting a indoor unit from a control
group, select a unit to delete from the
Registered list
q
and press [>>] button
r
.
(The deleted unit is then relocated to the
Unregistered list
w
.)
4.
When registering a representative indoor unit,
select a unit in the Registered list
q
and
press the [Reg. Rep. Model] button
t
.
* mark is added to the top of the name of the
indoor unit selected as the representative one.
5.
When changing the order of display of indoor
units in the Registered list
q
, select a unit
and press [Up] or [Down] button
y
.
6.
Press [OK] button
u
to save the settings and
return to the Control group setting screen.
The settings will be saved when the [OK]
button in the Control group setting screen is
pressed.
Press [Cancel] button
o
to cancel the settings.
Setting error:
¡
When any of the following errors occurs during
setting, an error screen will appear.
¡
When no indoor units are registered.
(screen 2)
¡
When no representative unit is selected in the
indoor unit registration screen.
(screen 3)
[Restrictions]
A single indoor unit cannot be registered in two or
more control groups.
Setting of the FC Change Over
Screen 1 Registration of Indoor Unit
Screen 2 Confirm
Screen 3 Confirm
1
2
7
8
18
6
18
5
3
3
3
4
87
System Settings Menu Operation
NOTE:
¡
Always put the indoor unit that has the
cooling-heating switchover right on the
top. If not, the FC Change Over will not
properly work.
¡
Please do not set the indoor unit where
the room temperature changes often near
the window etc. as a representative
indoor unit for the prevention of hunting in
the FC Change Over.