5
|
Application guidelines
Installer reference guide
49
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
Current sensors can be used to limit the consumption of the heat pump on every
phase taking into account the set household fuse and the actual consumption of
other appliances.
Current sensors must be installed before the main fuses on each phase to make
use of this feature. This function can be useful in countries where the government
gives incentives to limit the fuse sizes.
C
i
t
CL
a
b
c
d
Ci
Current input
t
Time
CL
Current limit corresponding to fuse size
a
Current limitation active (no external load)
b
External load
c
Current limitation active (with external load)
d
Actual current input
Setup and configuration
See:
▪
The installation manual of the current sensors
▪
"To perform a current sensor phase check"
Wires: 3×2. Use part of the cable (40 m) delivered as accessory.
[9.9.1]=3 (
Power consumption control
=
Current sensor
)
[9.9.E]
Current sensor offset
5.6.5 BBR16 power limitation
INFORMATION
Restriction:
BBR16 settings are only visible when the language of the user interface is
set to Swedish.
NOTICE
2 weeks to change.
After you activated BBR16, you only have 2 weeks to change its
settings (
BBR16 activation
and
BBR16 power limit
). After 2 weeks, the unit
freezes these settings.
Note:
This is different from the permanent power limitation, which is always
changeable.
Use the BBR16 power limitation when you must comply with BBR16 regulations
(Swedish energy regulations).
You can combine the BBR16 power limitation with the other power consumption
controls. If you do so, the unit uses the most restrictive control.