6
|
Unit installation
Installer reference guide
60
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
4
Drain remaining water and brine from the hydro module. Open the water and
brine air purge valves at the top of the module to speed up the draining
process.
d
a
b
c
a
Water drain valve
b
Brine drain valve
c
Brine air purge valve
d
Water air purge valve
NOTICE
Ensure that no brine or water can fall into the switch box of the hydro module.
5
Perform the remaining steps as described in
57].
6.2.4 To close the indoor unit
1
If applicable, reinstall the left side panel.
2
If applicable, reinsert the hydro module.
3
If applicable, close the cover of the main switch box and reinstall the front
panel.
4
Close the cover of the installer switch box.
5
Reconnect the cables to the user interface panel.
6
Reinstall the user interface panel.
7
Reinstall the top panel.
NOTICE
When closing the indoor unit cover, make sure that the tightening torque does NOT
exceed 4.1 N•m.
6.3 Mounting the indoor unit
6.3.1 About mounting the indoor unit
When
Mount the indoor unit before you connect the brine and water piping.