5
|
Application guidelines
Installer reference guide
51
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
▪
Setup and configuration: See
"8.2.2 To connect the remote outdoor
88] (+ the installation manual of the remote outdoor sensor
(delivered as accessory)).
5.8 Setting up passive cooling
INFORMATION
Restriction:
Passive cooling is only possible for:
▪
Heating only models
▪
Brine temperatures between 0 and 20°C
Passive cooling is cooling without using the compressor. Here the brine circuit
must be branched over the cooling fan coils.
Setup
a
b
b
c
d
e
h
g
f
a
Thermostat
b
Fan coil units
c
External circulation pump
d
Non-return valve
e
Brine pump
f
Plate heat exchanger
g
Hydro
h
Remote outdoor sensor
▪
A thermostat input contact creates a demand for the brine pump to run. For
more information, see
"8.2.12 To connect the thermostat for passive
▪
An external circulation pump is required and needs to be controlled by the
external thermostat.
▪
A non-return valve must prevent backflow to the inlet of the passive cooling loop
and force the brine to go through the borehole.
Configuration
None.