8
|
Electrical installation
Installer reference guide
91
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
1
Open the following (see
"6.2.2 To open the indoor unit"
1
Top panel
1
3
2
2
User interface panel
3
Installer switch box cover
2
Connect the domestic hot water pump cable to the appropriate terminals as
shown in the illustration below.
1~
M
M2P
1×
2×
X2M
1×
1 2
3
Fix the cable with cable ties to the cable tie mountings.
8.2.6 To connect the alarm output
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
[9.D]
Alarm output
1
Open the following (see
"6.2.2 To open the indoor unit"
1
Top panel
3
2
5
1
4
2
User interface panel
3
Front panel
4
Installer switch box cover
5
Main switch box cover
2
Connect the alarm output cable to the appropriate terminals as shown in the
illustration below. Make sure to put wires 2 and 3 between the installer switch
box and main switch box in a cable sleeve (field supply) so that they are
double insulated.