10
|
Configuration
Installer reference guide
190
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
[D‑00]
Backup heater
Compressor
0
Forced OFF
Forced OFF
2
Allowed
Power consumption control
Power consumption control
See
24] for detailed information about this
functionality.
#
Code
Description
[9.9.1]
[4-08]
Power consumption control
:
▪
0
No
: Disabled.
▪
1
Continuous
: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
▪
2
Inputs
: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
▪
3
Current sensor
: Enabled: You can set a
current limitation value (in A) to which the
household current will be limited.
Continuous power consumption control and power consumption control with
digital inputs
The type of limit needs to be set in combination with the continuous power
consumption control and the power consumption control with digital inputs.
#
Code
Description
[9.9.2]
[4-09]
Type
:
▪
0
Amp
: The limitation values are set in A.
▪
1
kW
: The limitation values are set in kW.
Limit when [9.9.1]=
Continuous
and [9.9.2]=
Amp
:
#
Code
Description
[9.9.3]
[5-05]
Limit
: Only applicable in case of full time
current limitation mode.
0 A~50 A
Limits when [9.9.1]=
Inputs
and [9.9.2]=
Amp
:
#
Code
Description
[9.9.4]
[5-05]
Limit 1
: 0 A~50 A
[9.9.5]
[5-06]
Limit 2
: 0 A~50 A
[9.9.6]
[5-07]
Limit 3
: 0 A~50 A
[9.9.7]
[5-08]
Limit 4
: 0 A~50 A
Limit when [9.9.1]=
Continuous
and [9.9.2]=
kW
: