120
Parameter
Note
the current image.
Manual: users can set the color of high and low temperature by
themselves.
Alarm
Condition
Single
When you select “Hot spot temperature more than”, it means it will
trigger alarm when the temperature is higher than the temperature
which has been set.
When you select “Cold spot temperature less than”, it means it will
trigger alarm when the temperature is less than the temperature which
has been set.
If you select both at the same time, it means it will trigger alarm if it
can meet either.
Combination
It will trigger alarm when the highest temperature is higher than the
temperature set by users and lowest temperature is lower than the
temperature set by users.
PTZ
When alarm happens, the video monitoring image link will switch to the
selected preset, tour and pattern or hybrid linkage.
Hybrid link is valid only it is within the time of link schedule; please refer to
“6.4.6 Link Schedule”.
Note:
The PTZ link is valid after PTZ setting is completed, please refer to
“3 PTZ”
for more details.
Sheet 6-36
Step 4
Click
“Save” to make config valid. Please see Figure 6-56 for more details after config is valid.