Operation
7-10
Warning Description
Explanation
“Helium Temp Running High!”
Helium discharge temperature approaching high error set point;
check cooling water temperatures, may also be caused by low
oil level check compressor module sight glasses or low oil
temperature caused by cool water
“Oil Temp Running High!”
Oil temperature approaching high error set point; verify cooling
water flow and temperatures
“Oil Temp Running Low!"
Oil temperature approaching low error set point; verify cooling
water flow and temperatures (reduce flow rate or increase
temperature)
7.7.7 Error and warning set points
The trip and clear set points for all the errors and warnings are listed in the following table.
Error Message
Lock Out
Contributor?
Trip
Clear
"High pressure too High!"
YES
400 psig (27.6bar)
375 psig (25.9 bar)
"High pressure too Low!"
YES
150 psig (10.3bar)
170 psig (11.7 bar)
“Low Pressure Too Low!”
YES
40 psig (2.8 bar)
50 psig (3.4 bar)
“Low Pressure Too High!"
YES
250 psig (17.2 bar)
240 psig (16.5 bar)
"Delta Pressure Too High!"
YES
300 psig (20.7bar)
290 psig (20bar)
"Delta Pressure Too Low!"
YES
50 psig (3.4 bar)
75 psig (5.2 bar)
"Static Pressure Too High!"
YES
300 psig (20.7 bar)
280 psig (19.3 bar)
"Static Pressure Too Low!"
YES
100 psig (6.9 bar)
170 psig (11.7 bar)
"Water In Temp Too High"
YES
110 °F (43 °C)
80 °F (27 °C)
"Water In Temp Too Low"
YES
40 °F (4 °C)
50 °F (10 °C)
“Water Out Temp Too High!”
YES
125 °F (52 °C)
110 °F (43 °C)
"Water Out Temp Too Low"
YES
40 °F (4 °C)
50 °F (10 °C)
“Helium Temp Too High!”
YES
190 °F (88 °C)
120 °F (49 °C)
“Helium Temp Too Low!"
YES
40 °F (4 °C)
50 °F (10 °C)
“Oil Temp Too High!”
YES
125 °F (52 °C)
110 °F (43 °C)
“Oil Temp Too Low!"
YES
40 °F (4 °C)
50 °F (10 °C)
“Compressor Motor Current Too
Low!”
YES
< 5A
≥ 5 A
Содержание CPA289C
Страница 1: ...CP PT410 CPA289C C Cryocooler PT410 CPA289C INSTALLATION and OPERATION MANUAL ...
Страница 4: ...1 100 D Section 1 Overview ...
Страница 7: ...2 100 C Section 2 Warranty ...
Страница 10: ...3 100 B Section 3 Safety ...
Страница 17: ...4 100 B Section 4 Inspection and Unpacking ...
Страница 20: ...05 PT410 CPA289C B Section 5 Specifications ...
Страница 31: ...Specifications 5 11 Figure 5 6 System I O wiring diagram ...
Страница 32: ...Specifications 5 12 Figure 5 7 System I O wiring diagram external supply ...
Страница 33: ...Specifications 5 13 5 4 Cold head drawing Figure 5 8 Cold Head Drawing ...
Страница 34: ...6 100 E Section 6 Installation ...
Страница 36: ...Installation 6 2 Inspect the cold head Figure 6 2 Outline drawing of standard cold heads A E D C B F ...
Страница 45: ...7 100 C Section 7 Operation ...
Страница 58: ...8 100 C Section 8 Routine Maintenance ...