Figure 70. Circuit Breakers for Cabinet (left) and Blower (right)
a. Close the rear door of the cabinet.
b. Enter the following command in a terminal window on the SMW:
smw$
xtcli power up Hostname
Hostname
is the cabinet, system, or partition ID; examples include
c0-0
(for a cabinet),
S0
(for a
system), or
p0
(for a partition).
2.18 Non-spring Returned Water Valve Actuator Replacement
2.18.1 Remove a Non-Spring Returned Water Valve Actuator
Prerequisites
Tools Required:
Diagonal cutter
Tie straps
Phillips screwdriver
Hex-head tool
Time Required:
8-10 minutes
About this task
CAUTION:
●
Equipment damage
●
It's recommended to perform this procedure on a powered down cabinet. If performed on a powered
up cabinet, the actuator must be replaced within 15-20 minutes to prevent possible system EPO and/
or condensation.
CAUTION:
●
Equipment damage
System Cabinet Procedures
75