Chapter 5 Troubleshooting
5.1 System Reset Switch
The system reset switch is located above the RS485 COM1 port. The location is shown in Figure 16. It is used
to reset the network configuration.
System Reset
Switch
Figure 16
Reset Switch Location
5.1.1 Resetting the Network Configuration (Not SP4 Telzone
Programmer 2 Programmed)
Resetting the network configuration is done when it appears that the paging system is corrupt or an SP4-
APS splitter has been added, removed or replaced. Should one of these conditions occur, and the SP4-TZC
has not been programmed using the SP4 Telzone Programmer 2 software, perform this procedure. If you
have made changes, use Appendix A at the end of this manual to update the new Zone Code location for
each zone and zone group.
The procedure is as follows:
Remove the enclosure cover from the SP4-TZC.
Make sure 24VDC is
ON
to the SP4-TZC and all SP4-APS splitters.
Press and hold the system reset button for approximately 5 seconds until the all LED indicators
except the “POWER” LED indicator turns
OFF
.
Release the system reset button. The SP4-TZC will begin finding and mapping the SP4-APS
splitters. The “RS485 COM1 ACTIVE” LED indicator should be
BLINKING
. The
“STANDBY/RUN” LED will
BLINK
for a maximum of 1 minute after which the
“STANDBY/RUN” LED will remain
ON
.
Install the enclosure cover.
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5